The effect of passive filter on the 3rd, 5th and 7th harmonic in nonlinear load /

This project discusses the effect of passive filter on 3rd, 5th and 7th harmonic in nonlinear load. The passive filter considered is the single tuned harmonic filter. In the design of the filter, the passive elements of the filter are derived. Studies are made to investigate the effectiveness of usi...

Descrizione completa

Salvato in:
Dettagli Bibliografici
Autore principale: Mohd Haniff Roslan (Autore)
Natura: Tesi Software eBook
Lingua:English
Pubblicazione: Kangar, Perlis School of Electrical System Engineering, University Malaysia Perlis 2011
Soggetti:
Tags: Aggiungi Tag
Nessun Tag, puoi essere il primo ad aggiungerne! !
Descrizione
Riassunto:This project discusses the effect of passive filter on 3rd, 5th and 7th harmonic in nonlinear load. The passive filter considered is the single tuned harmonic filter. In the design of the filter, the passive elements of the filter are derived. Studies are made to investigate the effectiveness of using single tuned filter in reducing harmonic distortions and also to determine the optimal location of installing the filters. The effects of power factor correction capacitor and load parameters variation on harmonic distortion are also investigated. Simulation results show that the single tuned filter is effective in reducing harmonics. The study also proves that passive filter give better performance in reducing harmonics when it is placed close to the harmonic producing loads.
Descrizione fisica:1 CD-ROM 12 cm